CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
3.1.20 Digital output type coding
type dig out selection
XXXXXXXX XXXXXX00 dig out 1 pulse (default type out 1)
XXXXXXXX XXXXXX01 dig out 1 control
XXXXXXXX XXXXXX10 dig out 1 alarm
XXXXXXXX XXXX00XX dig out 2 pulse (default type out 2)
XXXXXXXX XXXX01XX dig out 2 control
XXXXXXXX XXXX10XX dig out 2 alarm
XXXXXXXX XX00XXXX dig out 3 pulse (default type out 3)
XXXXXXXX XX01XXXX dig out 3 control
XXXXXXXX XX10XXXX dig out 3 alarm
XXXXXXXX 00XXXXXX dig out 4 pulse (default type out 4)
XXXXXXXX 01XXXXXX dig out 4 control
XXXXXXXX 10XXXXXX dig out 4 alarm
XXXXXX00 XXXXXXXX pulse 1 Kwh+ (default) (see note 1)
XXXXXX01 XXXXXXXX pulse 1 Kwh- (see note 1)
XXXXXX10 XXXXXXXX pulse 1 Kvarh+ (see note 1)
XXXXXX11 XXXXXXXX pulse 1 Kvarh- (see note 1)
XXXX00XX XXXXXXXX pulse 2 Kwh+ (default) (see note 1)
XXXX01XX XXXXXXXX pulse 2 Kwh- (see note 1)
XXXX10XX XXXXXXXX pulse 2 Kvarh+ (see note 1)
XXXX11XX XXXXXXXX pulse 2 Kvarh- (see note 1)
XX00XXXX XXXXXXXX pulse 3 Kwh+ (default) (see note 1)
XX01XXXX XXXXXXXX pulse 3 Kwh- (see note 1)
XX10XXXX XXXXXXXX pulse 3 Kvarh+ (see note 1)
XX11XXXX XXXXXXXX pulse 3 Kvarh- (see note 1)
00XXXXXX XXXXXXXX pulse 4 Kwh+ (default) (see note 1)
01XXXXXX XXXXXXXX pulse 4 Kwh- (see note 1)
10XXXXXX XXXXXXXX pulse 4 Kvarh+ (see note 1)
11XXXXXX XXXXXXXX pulse 4 Kvarh- (see note 1)
NOTE 1: the multiplier type depends on the “info P” variable (refer to the instantaneous variables
map).
3.1.21 Info out (1,2,3,4) coding
info out Selection
XXXXXXXX XX000000 Variable type(from 000000 to 110100, see table 3.1.1)
XXXXXX00 00XXXXXX Control type «up» (default)
XXXXXX00 01XXXXXX Control type «up.l»
XXXXXX00 10XXXXXX Control type «do»
XXXXXX00 11XXXXXX Control type «do.l»
XXXXX0XX XXXXXXXX Normally de-energised relay
XXXXX1XX XXXXXXXX Normally energised relay
3.1.22 Daylight saving time coding
Tariff management Selection
XXXXXXXX XXXXXX00 ON
XXXXXXXX XXXXXX01 OFF
0101XXXX XXXXXXXX bit check