CARLO GAVAZZI WM4-96 - PROGRAMMING Manual de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 57
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
21
CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
NOTE:
1
According to the selected electrical system, the voltages can be Phase to Phase Voltage or Phase
to Neutral Voltages.
2
Negligible values when the selected system is without neutral.
All the variables of the previous table are contiguous. Note that using a single read command it is
possible to read at most 120 words.
The values of the harmonic and distortion variables are represented as short (2 byte long). The
decimal point must be set to “111.1” for distortion and angle variables (THD, THDo, THDe), and to
111.11” for the harmonic variables (h).
The stored values have physical meaning only if the harmonic analysis of the relevant phase is
enabled (please refer to the user manual for FFT enable function, see also EEPROM map, address
200Ch).
Example 17: reading of the VL1 3
rd
order harmonic
“Value” request frame (frame 8 byte):
01h
04h
02h
5Ch
00h
01h
CRC
CRC
“Value” answer frame (frame 7 byte):
01h
04h
02h
13h
0Dh
CRC
CRC
Variable value: 0D13h 3347 (decimal)
Value format: 111.11
VL1 3
rd
order harmonic value 33.47% (the display shows 33.4%)
Example 18: reading of the phase 1 - 3
rd
order relative angle
“Value” read request frame (frame 8 byte):
01h
04h
02h
68h
00h
01h
CRC
CRC
“Value” read answer frame (frame 7 byte):
01h
04h
02h
EFh
06h
CRC
CRC
Variable value: 06EFh 1775 (decimal)
Value format: 111.1
Phase 13
rd
order relative angle:177.5° (the display shows 177°)
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]