CARLO GAVAZZI WM4-96 - PROGRAMMING Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 57
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
12
CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
1000000000*0 = 0
(- 42604 + 0*1000000000)/100 = - 426.04 kWh
2.6 WRITING OF THE ENERGY METER VALUES
The user is not allowed to write in the energy meter memory area. It is only possible to reset the
energy meter using fixed frames.
2.7 ENERGY METERS RESET COMMANDS
The fixed frames to be used to reset the energy meters are listed below:
1. General reset command (reset of all the total, partial and monthly meters)
Reset request frame (8 byte):
01h
06h
00h
ECh
D4h
F0h
CRC
CRC
Reset answer frame (8 byte):
01h
06h
00h
ECh
D4h
F0h
CRC
CRC
2. Total positive energy meters (kWh+ and kvarh+) and monthly meters reset command
Reset request frame (8 byte):
01h
06h
01h
00h
A5h
F0h
CRC
CRC
Reset answer frame (8 byte):
01h
06h
01h
00h
A5h
F0h
CRC
CRC
3. Total negative energy meters (kWh- and kvarh-) and monthly meters reset command
Reset request frame (8 byte):
01h
06h
01h
04h
23h
44h
CRC
CRC
Reset answer frame (8 byte):
01h
06h
01h
04h
23h
44h
CRC
CRC
4. Partial positive energy meters (kWh+ and kvarh+) and monthly meters reset command
Reset request frame (8 byte):
01h
06h
01h
08h
87h
35h
CRC
CRC
Reset answer frame (8 byte):
01h
06h
01h
08h
87h
35h
CRC
CRC
5. Partial negative energy meters (kWh- and kvarh-) and monthly meters reset command
Reset request frame (8 byte):
01h
06h
01h
C0h
59h
12h
CRC
CRC
Reset answer frame (8 byte):
01h
06h
01h
C0h
59h
12h
CRC
CRC
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]