SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
3 EEPROM VARIABLE MAP
NOTE: f.s. means full scale; b.s. means beginning of the scale
WM4-96 configuration map
ADD. VARIABLE MAX MIN DEFAULT BIT CHECK
2000 Password 500 0 0 0101XXXX XXXXXXXX
2002 System 4 0 2 0101XXXX XXXXXXXX
2004 CT 60000 1 10 not present
2006 VT 60000 1 10 not present
2008 type avg 1 0 0 0101XXXX XXXXXXXX
200A time avg 30 1 15 0101XXXX XXXXXXXX
200C enable FFT
See EEPROM data format tables
0100XXXX XXXXXXXX
200E type digit 1 0 0 0101XXXX XXXXXXXX
2010 field 1 e 2
See EEPROM data format tables
0101XXXX XXXXXXXX
2012 field 3 e 4
See EEPROM data format tables
0101XXXX XXXXXXXX
2014 RS485: address 255 1 1 not present
2016 RS485: baud rate 3 0 3 (9600) not present
2018 RS485: parity 2 0 0 (none) not present
201A RS232: baud rate 3 0 3 (38400)
not present
201C Reserved
201E filter range 1000 1 10 not present
2020 filter coefficient 255 1 3 not present
2022 event selection
See EEPROM data format tables
not present
2024 event selection
See EEPROM data format tables
not present
2026 F.S. digital input
See EEPROM data format tables
0101XXXX XXXXXXXX
2028
USA/EUROclockformat See EEPROM data format tables
0101XXXX XXXXXXXX
202A Language
See EEPROM data format tables
not present
202C
Pulse-retransmitted
tariff
See EEPROM data format tables
not present
202E Inputs type
See EEPROM data format tables
0101 see note 1
2030
Data log time interval
60 1 15 0101XXXX XXXXXXXX
2032 ---
2034 ---
2036 Enabled dig.inputs
See EEPROM data format tables
see note 1
2038 Pulses/m
3
Gas 1000 1 1
203A Pulses/m
3
Water 1000 1 1
203C dmd tariff alarm 4 0 0 0101XXXX XXXXXXXX
203E Dig. out type
See EEPROM data format tables
not present
2040 Pulses/kWh out1 1000 1 1 01XXXXXX XXXXXXXX
2042 Pulses/kWh out2 1000 1 1 01XXXXXX XXXXXXXX
2044 Pulses/kWh out3 1000 1 1 01XXXXXX XXXXXXXX
2046 Pulses/kWh out4 1000 1 1 01XXXXXX XXXXXXXX
2048 Info dig. out 1
See EEPROM data format tables
not present
204A Delay out 1 255 0 0 0101XXXX XXXXXXXX
204C Set-point out 1 f.s b.s. 0 not present
204E Hysteresis out 1 f.s 0 0 not present
2050 Info dig. out 2
See EEPROM data format tables
not present
2052 Delay out 2 255 0 0 0101XXXX XXXXXXXX
2054 Set-point out 2 f.s b.s. 0 not present
2056 Hysteresis out 2 f.s 0 0 not present
2058 Info dig. out 3
See EEPROM data format tables
not present
205A Delay out 3 255 0 0 0101XXXX XXXXXXXX
205C Set-point out 3 f.s b.s. 0 not present
205E Hysteresis out 3 f.s 0 0 not present
2060 Info dig. out 4
See EEPROM data format tables
not present
2062 Delay out 4 255 0 0 0101XXXX XXXXXXXX
2064 Set-point out 4 f.s b.s. 0 not present
2066 Hysteresis out 4 f.s 0 0 not present