28
CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
3.1.16 Pulse type selection
Pulse type selection Selection
XXXXXXXX XXXXX000 Out 1 pulses related to: total energy meter
XXXXXXXX XXXXX001 Out 1 pulses related to: period 1 energy meter
XXXXXXXX XXXXX010 Out 1 pulses related to: period 2 energy meter
XXXXXXXX XXXXX011 Out 1 pulses related to: period 3 energy meter
XXXXXXXX XXXXX100 Out 1 pulses related to: period 4 energy meter
XXXXXXXX XX000XXX Out 2 pulses related to: total energy meter
XXXXXXXX XX001XXX Out 2 pulses related to: period 1 energy meter
XXXXXXXX XX010XXX Out 2 pulses related to: period 2 energy meter
XXXXXXXX XX011XXX Out 2 pulses related to: period 3 energy meter
XXXXXXXX XX100XXX Out 2 pulses related to: period 4 energy meter
XXXXXXX0 00XXXXXX Out 3 pulses related to: total energy meter
XXXXXXX0 01XXXXXX Out 3 pulses related to: period 1 energy meter
XXXXXXX0 10XXXXXX Out 3 pulses related to: period 2 energy meter
XXXXXXX0 11XXXXXX Out 3 pulses related to: period 3 energy meter
XXXXXXX1 00XXXXXX Out 3 pulses related to: period 4 energy meter
XXXX000X XXXXXXXX Out 4 pulses related to: total energy meter
XXXX001X XXXXXXXX Out 4 pulses related to: period 1 energy meter
XXXX010X XXXXXXXX Out 4 pulses related to: period 2 energy meter
XXXX011X XXXXXXXX Out 4 pulses related to: period 3 energy meter
XXXX100X XXXXXXXX Out 4 pulses related to: period 4 energy meter
3.1.17 Input type coding
Field Selection
XXXXXXXX XXXXXXX0 Measure (from analogue input module)
XXXXXXXX XXXXXXX1 Pulse (pulses from official watthourmeter)
0101XXXX XXXXXXXX bit check
3.1.18 Enabled digital input coding
Diginput_on Selection
------- --- --- --X Input A1 (1=enabled, 0=disabled)
------- --- --- -X- Input A2 (1=enabled, 0=disabled)
------- --- --- X--
Input A3 (1=enabled, 0=disabled)
------- --- --X --- Input C1 (1=enabled, 0=disabled)
------- --- -X- ---
Input C2 (1=enabled, 0=disabled)
------- --- X-- --- Input C3 (1=enabled, 0=disabled)
------X --- --- --- Input A2 (1=dual tariff gas metering, 0=water metering)
-----X- --- --- --- Inputs A1 and A2
(1=negative energies metering, 0=gas and water metering)
3.1.19 Coding of the tariff associated to the Wdmd alarm
Alarm tariff Selection
------- --- --- XXX Tariff of alarm 1 (from 0 to 4, 0 means total)
------- --- XXX --- Tariff of alarm 2 (from 0 to 4, 0 means total)
------- XXX --- ---
Tariff of alarm 3 (from 0 to 4, 0 means total)
----XXX --- --- --- Tariff of alarm 4 (from 0 to 4, 0 means total)
0101XXXX XXXXXXXX bit check