SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
3.1.4 FFT enable coding
FFT enable selection
XXXXXXXX XXXXXX11 fft V1-I1 disable
XXXXXXXX XXXXXX00 fft V1-I1 enable
XXXXXXXX XXXX11XX fft V2-I2 disable
XXXXXXXX XXXX00XX fft V2-I2 enable
XXXXXXXX XX11XXXX fft V3-I3 disable
XXXXXXXX XX00XXXX fft V3-I3 enable
3.1.5 Digit type coding
digit type Selection
XXXXXXXX XXXXXXX0 4 digit visualisation
XXXXXXXX XXXXXXX1 3½ digit visualisation
3.1.6 Field n coding
The field n (n = 0, 1, 2, 3) variables are the variables chosen by the user to be shown on page 0 of
the WM4 display.
3.1.7 Field (1 and 2) coding
Field Selection
XXXXXXXX XX000000 field 1 variable
XXXX0000 00XXXXXX field 2 variable
0101XXXX XXXXXXXX bit check
3.1.8 Field (3 and 4) coding
Field Selection
XXXXXXXX XX000000 field 3 variable
XXXX0000 00XXXXXX field 4 variable
0101XXXX XXXXXXXX bit check
3.1.9 RS485 baud rate coding
RS485 baud rate Selection
XXXXXXXX XXXXXX00 1200b
XXXXXXXX XXXXXX01 2400b
XXXXXXXX XXXXXX10 4800b
XXXXXXXX XXXXXX11 9600b
3.1.10 RS485 parity coding
RS485 parity Selection
XXXXXXXX XXXXXX00 None
XXXXXXXX XXXXXX01 Odd
XXXXXXXX XXXXXX10 Even