ENGLISH
Hi.A (%) = 100 x ?V that in our example corresponds to:
10
100 x 5V/10 = 50%, therefore enter 50.00.
Also in this case, as per the electrical and displayed scale, it is possible
to invert the scale, that is, a decreasing value of the retransmitted signal
may correspond to an increasing value of the input variable
S.ou:: menu to program the serial outputs parameters
MDI40 is provided (on request) with an RS485 serial interface that allows
the communication with a PC or PLC. It is possible to retransmit both the
static and the dynamic variables and make connections with more than
one MDI40 (multidrop).
Add : address value programmable within the range: 1 < Add < 255.
b.dr : baud rate programming of the data, see table S.ou in the flow-
chart.
For further information on the serial interfacing, see the special literature.
Diagnostic messages
EEE blinking indication: burn-out or overcoming of the displaying
range (value to be displayed > 3999).
-EE blinking indication: burn-out or overcoming of the displaying range
(value to be displayed > -1999).
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]