
21
ENGLISH
do.L : down/low alarm set-point with latch function. The alarm func-
tions as per “do” and can be reset only manually when the F key
is pressed for at least 2 seconds during the measuring phase.
Lo.S : minimum set-point value, which is programmable within the
range: Lo (Hi) < Lo.S < Hi (Lo). This limit to the set-point’s amplitude is
very useful when the set-points are managed outside the programming
phase.
Hi.S : maximum set-point value, which is programmable within the
range: Lo.S < Hi.S < Hi (Lo). This limit to the set-point’s amplitude is very
useful when the set-points are managed outside the programming
phase.
SEt : value of the alarm set-point to be programmed within the
following range: Lo.S < SEt < Hi.S.
HYS : hysteresis value of the set-point. The hysteresis is a numerical
value included within the range: 0 < HYS < 3999 and represents the
difference between the value of the ON alarm status and the value of the
OFF alarm status. The hysteresis modifies the value of the OFF alarm
status not only with regards to the set alarm value, but also with regards to
the alarm type: the hysteresis value is summed to the set value if the alarm
type is “do” and subtracted from the set value if the alarm type is “uP”.
Example:
“do” alarm, “SEt”=2200 (value of the ON alarm status), hysteresis
“HYS”=12⇒ resulting OFF value (end of alarm status): 2212 (resulting
from 2200 +12).
“uP” alarm, “SEt”=2200 (value of the ON alarm status), hysteresis
“HYS”=12 ⇒ resulting OFF value (end of alarm status): 2188 (resulting
from 2200 - 12).
Comentarios a estos manuales