CARLO GAVAZZI MDI 40 TF - CONFIGURATION SOFTWARE Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 27
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
20
ENGLISH
according to the following relationship: °F = (1.8 x °C) + 32.
Example: Lo.E=-50°C Lo=-58°F; Hi.E=+760°C Hi=+1400°F,
means that the new measuring range becomes -58° to +1400°F. The
data to be entered in the displayed scale can be calculated either by
means of the above mentioned °F relationship, or using the data of the
relevant measuring range (see chapter Technical Features, paragraph
Inputs temperature on the previous page).
SP.1/SP.2 : menu to select the programming of the set-point parameters.
tYP : selection of the type of control.
oFF : signalling of the abnormal condition. The relay is activated when
a burn-out condition occurs or the measurement is outside the electrical
range (displaying and blinking of the measured value or displaying of the
EEE/ -EE message).
Note: by selecting this function the Lo.S, Hi.S, SP.1, HYS param-
eters are not active.
do : down/low alarm set-point. The relay will be activated when the
measured value goes below the set-point value.
uP : up/high alarm set-point. The relay will be activated when the
measured value goes over the set-point value.
d.do : alarm set-point similar to do, but with alarm inhibition eventually
present when MDI40 is turned on. The control starts only after the first
condition of non-alarm has been signalled.
uP.L : up/high alarm set-point with latch function.
The alarm functions as per uP, but the alarm can be reset only manually
when the F key is pressed for at least 2 seconds during the measuring
phase.