20
ENGLISH
according to the following relationship: °F = (1.8 x °C) + 32.
Example: “Lo.E”=-50°C ⇒ “Lo”=-58°F; “Hi.E”=+760°C ⇒ “Hi”=+1400°F,
means that the new measuring range becomes -58° to +1400°F. The
data to be entered in the displayed scale can be calculated either by
means of the above mentioned “°F” relationship, or using the data of the
relevant measuring range (see chapter “Technical Features”, paragraph
“Inputs temperature” on the previous page).
SP.1/SP.2 : menu to select the programming of the set-point parameters.
tYP : selection of the type of control.
oFF : signalling of the abnormal condition. The relay is activated when
a burn-out condition occurs or the measurement is outside the electrical
range (displaying and blinking of the measured value or displaying of the
“EEE”/ “-EE” message).
Note: by selecting this function the “Lo.S”, “Hi.S”, “SP.1”, “HYS” param-
eters are not active.
do : down/low alarm set-point. The relay will be activated when the
measured value goes below the set-point value.
uP : up/high alarm set-point. The relay will be activated when the
measured value goes over the set-point value.
d.do : alarm set-point similar to “do”, but with alarm inhibition eventually
present when MDI40 is turned on. The control starts only after the first
condition of non-alarm has been signalled.
uP.L : up/high alarm set-point with latch function.
The alarm functions as per “uP”, but the alarm can be reset only manually
when the F key is pressed for at least 2 seconds during the measuring
phase.