SERIAL COMMUNICATION PROTOCOL
WM24-96
V1 R0
Page
6
2 RAM VARIABLES MAP
2.1 INSTANTANEOUS VARIABLES MAP (RAM, PAGE 1)
ADDRESS BYTE VARIABLE Type ADDRESS BYTE VARIABLE Type
1
0200
2 V L1-N V
25
0239
3 W dmd P
2 0202 2 V L2-N V 26 023C 2 Hz H
3 0204 2 V L3-N V 27 023E 1 Unit V inf
4
0206
2 A L1 A
28
023F
1 Unit A inf
5 0208 2 A L2 A 29 0240 1 Unit P inf
6
020A
2 A L3 A
30
4 Wh (tot) E
7 020C 3 W L1 P 31
0241*
4 Wh + E
8 020F 3 W L2 P 32 4 varh (tot) E
9
0212
3 W L3 P
33
0245*
4 Wh - E
10 0215 3 var L1 P 34 4 Wh (t1) E
11
0218
3 var L2 P
35
0249*
4 varh C+ E
12 021B 3 var L3 P 36 4 varh (t1) E
13 021E 3 VA L1 P 37
024D*
4 varh C- E
14
0221
3 VA L2 P
38
1 Asy V D
15 0224 3 VA L3 P 39
0251
16
0227
1 PF L1 C
40
17 0228 1 PF L2 C 41
18 0229 1 PF L3 C 42
19
022A
2
V
V
43
20 022C 3
W
P 44
21
022F
3
var
P
45
22
0232
3
VA
P
46
23 0235 1
PF
C 47
24
0236
3 VA dmd P
NOTE *: the variable stored in this address is depending on the parameter “counter”.
NOTE: all the variables in this table are contiguous. It is possible to read more variables at a time,
up to 12 words at a time. Other maximum values are stored in the page 0 of the RAM.
2.1.1 Variable format
The value of all the instantaneous variables is stored as two’s complement integer value. It is
possible to read the C-, D- and H-type variables with a single read command, while two read
command are requested for V-, A- and P-type variables (variable and decimal point position).
The decimal point and the multiplier have to be set according to the Unit V, Unit A, Unit P word
coding (see the following table) for voltage (V), current (A) and power (P) variables, in the position
1111” for the D-type (%) variables, “11.11” for the H-type (Hz) variables, “111.1k” per the E-type
(energy) variables, “111.1” for the M-type (cubic meter) variables and in position 11.11 ” for the C-
type variables (PF). The single phase PF variables are stored with a positive value if the power
factor is “L” (inductive), and with a negative value if the power factor is “C” (capacitive). The variable
“PF “ has neither L nor C sign indication.
Decimal point and multiplier coding
INF value
d.p
INF value
d.p
3 1.111 8 111.1k
4 11.11 9 1111k
5 111.1 10 11.11M
6 1111 11 111.1M
7 11.11k 12 1111M