3.2.12 var_dig1 and var_dig2
MINIMUM MAXIMUM FORMAT
0 7 1111
VALUE CODE DESCRIPTION
0
W ∑
1
VA ∑
2
var ∑
3 W dmd
4 VA dmd
5
V ∑
6
PF ∑
7 ASY V
3.2.13 range_dig1 and range_dig2
MINIMUM MAXIMUM FORMAT
0 3
(1)
1111
This parameter is the multiplier associated to the setpoint of the digital outputs.
The real setpoint must be calculated as follows:
setpoint alarm 1 = dig_on1 * 10
range_dig1
The variable “setpoint alarm 1” is to be considered in the format of the relevant variable (in this
example var_dig1) which can be an A-, V-, P-, D- or C-type (see paragraph 2.1.1).
Note:
(1)
the maximum value of the multiplier is depending on the variable type and on the instrument
model according to the following table.
ModelVariable
100 VLL / 5A 208 VLL / 5A 400 VLL / 5A 660 VLL / 5A
W ∑
2 3 3 2
VA ∑
2 3 3 2
var ∑
2 3 3 2
W dmd 2 3 3 2
VA dmd 2 3 3 2
V ∑
1 2 2 1
PF ∑
0 0 0 0
ASY V 0 0 0 0