SERIAL COMMUNICATION PROTOCOL
WM24-96
V1 R0
Page
19
3.2.12 var_dig1 and var_dig2
MINIMUM MAXIMUM FORMAT
0 7 1111
VALUE CODE DESCRIPTION
0
W
1
VA
2
var
3 W dmd
4 VA dmd
5
V
6
PF
7 ASY V
3.2.13 range_dig1 and range_dig2
MINIMUM MAXIMUM FORMAT
0 3
(1)
1111
This parameter is the multiplier associated to the setpoint of the digital outputs.
The real setpoint must be calculated as follows:
setpoint alarm 1 = dig_on1 * 10
range_dig1
The variable “setpoint alarm 1” is to be considered in the format of the relevant variable (in this
example var_dig1) which can be an A-, V-, P-, D- or C-type (see paragraph 2.1.1).
Note:
(1)
the maximum value of the multiplier is depending on the variable type and on the instrument
model according to the following table.
ModelVariable
100 VLL / 5A 208 VLL / 5A 400 VLL / 5A 660 VLL / 5A
W
2 3 3 2
VA
2 3 3 2
var
2 3 3 2
W dmd 2 3 3 2
VA dmd 2 3 3 2
V
1 2 2 1
PF
0 0 0 0
ASY V 0 0 0 0
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]