
14
CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM24-96
V1 R0
Page
The active and reactive system powers are respectively calculated as algebraic sum of the single-
phase active and reactive powers.
The system power factor is without sign. Without any input signal, the single-phase power factors
are 0.00, the system one is 1.00.
2.2.9 Agreement concerning energy integration
The different meters, in function of the “counter” parameter, store the energy values integrating the
active or reactive power according to the following agreement.
1) KWh tot: integration of the system active power only in positive
2) Kvarh tot: integration of the module of the system reactive power
3) KWh +: integration of the sum of the positive single-phase active powers
4) KWh –: integration of the sum of the negative single-phase active powers
5) Kvarh C+: integration of the sum of the single-phase reactive powers in quadrant II
6) Kvarh C-: integration of the sum of the single-phase reactive powers in quadrant IV
7) Kvarh L+: integration of the sum of the single-phase reactive powers in quadrant I
8) Kvarh L-: integration of the sum of the single-phase reactive powers in quadrant III
2.2.10 Energy and utility meters limit
The energy meters have a fixed resolution of 0,1 kWh (or kvarh) with 19.999.999k as maximum
indication (from 0.0k to 1.999.999,9k and from 2.000.000k to 19.999.999k).
The utility meters have a fixed resolution of 0,1 m
3
with 1.999.999,9 m
3
as maximum indication.
When the maximum indication is reached, the meters are automatically reset.
Comentarios a estos manuales