SERIAL COMMUNICATION PROTOCOL
WM24-96
V1 R0
Page
Example 10: partial meters reset command
1-word write request command (8 byte):
01h 06h 01h 08h 87h 35h CRC CRC
Write answer command (8 byte):
01h 06h 01h 08h 87h 35h CRC CRC
The reset value is 0. The meters which are reset by this command are depending on the “counter”
parameter:
- counter=TOT-PAR Reset meters: kWh (t1), kvarh (t1)
kWh (t2), kvarh (t2)
kWh (t3), kvarh (t3)
kWh (t4), kvarh (t4)
- counter=TOT-1.CN Reset meters: m
3
gas (day), m
3
gas (night)
- counter=TOT-2.CN Reset meters: m
3
gas, m
3
water
Example 11: all meters reset command
1-word write request command (8 byte):
01h 06h 00h ECh D4h F0h CRC CRC
Write answer command (8 byte):
01h 06h 00h ECh D4h F0h CRC CRC
All the total and partial meters will be reset by this command.
2.2.8 Agreement concerning active and reactive power and power factor signs
Active and reactive power and power factor signs in WM24-96 are in accordance with the agreement
stated in enclosure E of the EN 61268 standard, as explained here below.
a : Exported active power
b : Imported active power
c : Imported reactive power
d : Exported reactive power
• The reference vector of the diagram is the
current one.
• The phase angle between vector V and
vector I is Ô.
• The phase angle Ô is to be considered
positive trigonometric-wise
(anticlockwise).