3.2 PROGRAMMING PARAMETERS
ADDRESS BYTE PARAMETER DESCRIPTION
0C8E 2 password Password
0C90 2 Vt_ratio Voltage transformer ratio
0C92
2 Ct_ratio Current transformer ratio
0C94
4 Pt_ratio Power transformation ratio
0C98 2 System System type
0C9A 2 P_int Integration period (dmd)
0C9C
2 Counter Meter working mode selection
0C9E 2 Pre_cn1 Meter 1 prescaler (gas)
0CA0 2 Pre_cn2 Meter 2 prescaler (gas)
0CA2 2 Pulse 1 Pulse rate, pulse output 1
0CA4
2 Pulse 2 Pulse rate, pulse output 2
0CA6 2 Sel_pul1 Meter associated to pulse output 1
0CA8 2 Sel_pul2 Meter associated to pulse output 2
0CAA
2 Sel_dig1 Digital output 1 working mode selection
0CAC
2 Var_dig1 Variable associated with the alarm output 1
0CAE 2 Range_dig1 Alarm 1 setpoint format
0CB0 2 Dig_on1 Alarm 1 activation setpoint
0CB2
2 Dig_off1 Alarm 1 deactivation setpoint
0CB4
2 Rel_type1 Normally energised/de-energised output 1
(ND/NE)
0CB6
2 Rel_delay1 Alarm 1 delay time
0CB8 2 Sel_dig2 Digital output 2 working mode selection
0CBA 2 Var_dig2 Variable associated with the alarm output 2
0CBC 2 Range_dig2 Alarm 2 setpoint format
0CBE
2 Dig_on2 Alarm 2 activation setpoint
0CC0 2 Dig_off2 Alarm 2 deactivation setpoint
0CC2 2 Rel_type2 Normally energised/de-energised output 2
(ND/NE)
0CC4 2 Rel_delay2 Alarm 2 delay time
0CC6 2 Address Address of the instrument (RS485)
0CC8
2 Filter_rng Operating range of the digital filter
0CCA
2 filter_coe Filtering coefficient
The maximum and minimum limits of the programmable parameters are listed below, together with
their meaning and format.
3.2.1 password
MINIMUM MAXIMUM FORMAT
0 1000 1111
Note: entering the value 782 the programming mode can be entered via keypad (reset password).
3.2.2 vt_ratio
MINIMUM MAXIMUM FORMAT
10 50000 111.1
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]