Vista de pagina 6
Mastergenerator ModBus Functions
2005 Carlo Gavazzi Industri A/S. All rights reserved.104
16384 4000 HI LO A1 Limit 1 Low Setup
16385 4001 HI LO A1 Limit 1 High Setup
16386 4002 HI LO A1 Limit 2 Low Setup
16387 4003 HI LO A1 Limit 2 High Setup
16388 4004 HI LO A2 Limit 1 Low Setup
4008 HI LO A3 Limit 1 Low Setup
16416 4020 HI LO B1 Limit 1 Low Setup
16892
41FC
HI Lo P8 Limit 1 Low Setup
16893
41FD
HI Lo P8 Limit 1 High Setup
16894
41FE
HI Lo P8 Limit 2 Low Setup
16895
41FF
HI Lo P8 Limit 2 High Setup
16896 4200 HI LO A1 on-delay tb Setup
16897 4201 HI LO A1 on-delay Setup
16898 4202 HI LO A1 off-delay tb Setup
16899 4203 HI LO A1 off Delay Setup
16900 4204 HI LO A2 on-delay tb Setup
16904 4208 HI LO A3 on-delay tb Setup
16928 4220 HI LO B1 on-delay tb Setup
17404
43FC
HI Lo P8 on-delay tb Setup
17405
43FD
HI Lo P8 on-delay Setup
17406
43FE
HI Lo P8 off-delay tb Setup
17407
43FF
HI Lo P8 off delay Setup
24576 6000 A1 HI: hour Lo: min On-time1 Setup
24577 6001 A1 hour Min Off-time 1 Setup
24578 6002 A1 xxx Days Day select 1 Setup
24579 6003 A1 xxx xxx Don’t-care Setup
24580 6004 A1 HI: hour Lo: min On-time 2 Setup
24581 6005 A1 hour Min Off-time 2 Setup
24582 6006 A1 xxx Days Day select 2 Setup
24583 6007 A1 xxx xxx Don’t-care Setup
24584 6008 A1 HI: hour Lo: min On-time3 Setup
24585 6009 A1 hour Min Off-time 3 Setup
24586 600A A1 x xx Days Day select 3 Setup
25587 600B A1 x xx x xx Don’t-care Setup
25588 600C A1 HI: hour Lo: min On-time 4 Setup
25589 600D A1 hour Min Off-time 4 Setup
25590 600E A1 x xx Days Day select 4 Setup
25591 600F A1 xxx xxx Don’t-care Setup
25592 6010 B1 HI: hour Lo: min On-time 1 Setup
26620 67FC P8 HI: hour Lo: min On-time 4 Setup
26621 67FD P8 hour Min Off-time 4 Setup
26622 67FE P8 xxx Days Day select 4 Setup
26623 67FF P8 x x x xx x Don’t-care Setup
49408 C100 A1 HI LO Pulse count
49409 C101 A2 HI LO Pulse count
49410 C102 A3 HI LO Pulse count
49411 C103 A4 HI LO Pulse count
49534 C17E P7 HI LO Pulse count
49535 C17F P8 HI LO Pulse count
Read AnaLink channels Set-Point values, as configured or as set by a previous
ModBus write-command.
Legal Values lies in the range from 0 to 255, and must be scaled according to
the type of analink signal.
Responds only, if channel is configured for AnaLink channeltype.
4 Registers per Setup.
Reading of 1 to 32 registers possible
If an attempt is made to read from a start-address and the number of registers
exceeds the allowed register range, no answer will be made, as this is interpreted
as an illegal function
Read Realtime channels Set-up values, as configured or as set by a previous
ModBus write-command.
Read On/Off times and day/holiday setup.
Responds only, if channel is configured for a Realtime channeltype.
16 Registers per Setup.
Reading of 1 to 32 registers possible
If an attempt is made to read from a start-address and the number of registers
exceeds the allowed register range, no answer will be made, as this is interpreted
as an illegal function.
Hour and Minutes in BCD
If Hour –value is read as FFh, then this setting is not active.
Days: MSB: Holiday
LSB: Monday
Read Pulse-counter Latched (Frozen) values
If an attempt is made to read from a start-address and the number of registers
exceeds the allowed register range, no answer will be made, as this is interpreted
as an illegal function.
Countvalue in BCD from 0 to 9999
Reading of 1 to 32 registers possible
Read timer channels Set-up ON and OFF delays, as configured or as set by a
p
revious ModBus write-command.
the delay-tb, if zero, the delay is counted in seconds. It tb = 1, the delay is
counted in minutes.
Responds only, if channel is configured for Timer channel type.
4 Registers per Setup.
Reading of 1 to 128 registers possible
If an attempt is made to read from a start-address and the number of registers
exceeds the allowed register range, no answer will be made, as this is interpreted
as an illegal function.