Mastergenerator ModBus Functions
2005 Carlo Gavazzi Industri A/S. All rights reserved.103
Dec Hex Mux Hi Lo Value
784 310 0HILO CD-0 In
ut Table
785 311 1HILO CD-1 In
ut Table
786 312 2HILO CD-2 In
ut Table
787 313 3HILO CD-3 In
ut Table
--- - - - In
ut Table
799 31F FHILO CD-F In
ut Table
800 320 0 H! LO EF-0 In
ut Table
815 32F FHILO EF-F In
ut Table
816 320 0HILO GH-0 In
ut Table
831 33F F HI LO GH-F In
ut Table
832 340 0HILO IJ-0 In
ut Table
847 34F F HI LO IJ-F In
ut Table
848 350 0HILO KL-0 In
ut Table
863 35F F HI LO KL-F In
ut Table
864 360 0 HI LO MN-0 In
ut Table
879 36F FHILO MN-F In
ut Table
880 370 0HILO OP-0 In
ut Table
895 37F F HI LO OP-15 In
ut Table
4096 1000 B8-B1 A8-A1 Digital
4097 1001 D C Digital
.. Digital
4103 1007 P O Digital
4112 1010 B8-B1 A8-A1 Digital
4113 1011 D C Digital
Digital
4119 1007 P O Digital
4880 1310 0 HI LO CD-0 In
ut Table
4881 1311 1 HI LO CD-1 In
ut Table
4882 1312 2 HI LO CD-2 In
ut Table
4883 1313 3 HI LO CD-3 In
ut Table
-.- - - - In
ut Table
4895 131F F HI LO CD-F In
ut Table
4896 1320 0 H! LO EF-0 In
ut Table
4911 132F F HI LO EF-F In
ut Table
4912 1330 0 HI LO GH-0 In
ut Table
4929 133F F HI LO GH-F In
ut Table
4930 1340 0 HI LO IJ-0 In
ut Table
4943 134F F HI LO IJ-F In
ut Table
4944 1350 0 HI LO KL-0 In
ut Table
4959 135F F HI LO KL-F In
ut Table
4960 1360 0 HI LO MN-0 In
ut Table
4975 136F F HI LO MN-F In
ut Table
4976 1370 0 HI LO OP-0 In
ut Table
4990 137F F HI LO OP-15 In
ut Table
8192 2000 HI LO Substatations
1..16
Status
8193 2001 HI LO Substations 17..32 Status
8194 2002 HI LO Substations 1.. 16 Status
8195 2003 HI LO Substations 17..32 Status
Dec Hex Hi Lo
8208 2010 Hour Minute 0..23 0..59 Setup
8209 2011 Second
s
Day of
week
0..59 0..FF Setup
8210 2012 Month Date 1..12 1..31 Setup
8211 2013 Year Year 0..99 0..99 Setup
Multiplexed analog Read Input Table
Registers 0300H to 037FH BCD-VALUES
Resisters 0400H to 047FH BINARY-VALUES
Multiplexed analog values only valid if Multiplexer is selected
Reading of 1 to 32 registers possible
Dupline group AB holds the actual Mux-address on the 4 most significant bits.
The remaining bits holds the digital transmit information from channel A5..B8
Active Devices found in the RS485 Network
32 bits indicating the presence of slaves in the Network
Register 2002h, MSB = Slave no 00 (central=0). LSB = Slave no 15
Register 2003h, MSB = Slave no 16 LSB = Slave no31.
2 Registers.
Reads information previously written by a Modbus command for transmission on
Dupline
Reading of 1 to 8 registers possible.
If an attempt is made to read from a start-address and the number of registers exceeds
the allowed register range, no answer will be made, as this is interpreted as an illegal
function
Reads information previously written by a Modbus command for forced output on
Dupline.
Reading of 1 to 8 registers possible.
If an attempt is made to read from a start-address and the number of registers exceeds
the allowed register range, no answer will be made, as this is interpreted as an illegal
function
Multiplexed Analog Read Output Table
Registers 1300H to 137FH BCD-VALUES
Resisters 1400H to 147FH BINARY-VALUES
Multiplexed analog values only valid if Multiplexer is selected
Reading of 1 to 32 registers possible
In the Binary Data-area, the transmitted data are checked against valid BCD coding and also the control-
its from the Analog transmitter.
Reading an “FFFF” indicates an invalid value or a non-existing analog transmitter.
Eg. Reading BCD data on Group C, then the channels C1 and C2 has to be active, before a binary value
are read. This is done automatically by the analog transmitters.
Active Devices found in Radio-Modem Network.
(When configured as Radio-modem Central)
32 bits indicating the presence of a Radio-Modem sbustation.
Register 2000h, MSB = Substation no 00 (central=0). LSB = Substation no 15
Register 2001h, MSB = Substation no 16 LSB = Substation no31.
2 Registers.
Read Generators internal 24 Hour clock.
Format: hh.mm, ss,dd,MM,DD,YYYY
Day of week: 1 Monday ..7 Sunday.
The Data format is BCD
ote: All 4 Registers must be read simultaneously.