18
ENGLISH
Lo.E : programming of the min. value of the electrical scale (see table
inP in the flow chart). Enter the minimum value that is to be measured
(zero scale).
Hi.E : programming of the max. value of the electrical scale (see table
inP in the flow chart). Enter the maximum value to be measured (full
scale).
NOTE: in the resistance measurements (inP rtd r5) the
maximum electrical full scale to be entered is: 1999 and the corre-
sponding value of Hi must be 199.9 in order to take resistance
measurements with a 0.1 resolution.
NOTE: if the measured variable goes beyond the scale limits Lo.E/
Hi.E, the value displayed during the measuring phase will be blinking
and updated with reference to the measured value up to the maximum
displaying range (dC and temperature measurements: -1999/1999;
AC and resistance measurements: 0/1999).
d.P : selection of the decimal point position in the Hi-Lo scale.
Lo : programming of the min. value of the displayed scale. Enter the
value to be displayed in correspondence with the minimum value of the
electrical scale Lo.E.
Example: Lo.E=4.00 mA Lo=100 mbar, means that when the value
measured by LDI35 is 4 mA, the displayed value will be 100 mbar.
Hi : programming of the max. value of the displayed scale. Enter the
value to be measured in correspondence with the maximum value of the
electrical scale Hi.E. Example: Hi.E=19.99 mA Hi=1800 mbar,
means that when the value measured by LDI35 is 20 mA, the displayed
value will be 1800 mbar.
NOTE: electrical scale and displayed scale must have:
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]