80
Current transformers and shunts
Dimensions
(mm) H x W x D
Input Specifications
Operating frequency
Max. system voltage
Rated insulation level
Security factor
Output Specifications
Secondary current
General Specifications
Class
Bus-bar size (mm)
Standards
Primary Current
Accuracy class depending
on the burden output
I2 nominal 1 A / 5 A
Ordering References
115.5 x 75 x 44
Current transformer
1-phase AC
40 to 60 Hz
0.72 kV
3 kV/1 min @ 50 Hz
≤5
5 A standard
(1 A on request)
0.5
25 x 3
IEC 60185
Burden (VA)
Class 0.5 1 3
1 A 10
5 A 10
10 A 10
15 A 10
25 A 10
40 A 10
See pag. 101
98.5 x 58 x 44
Current transformer
1-phase AC
40 to 60 Hz
0.72 kV
3 kV/1 min @ 50 Hz
≤5
5 A standard
(1 A on request)
0.5 / 1 / 3
20 x 8
IEC 60185
Burden (VA)
Class 0.5 1 3
40 A 3
50 A 3
60 A 3
80 A 3
100 A 3 4
150 A 3 4 6
200 A 3 4 6
250 A 5 8 10
300 A 5 8 10
See pag. 101
98.5 x 58 x 44
Current transformer
1-phase AC
40 to 60 Hz
0.72 kV
3 kV/1 min @ 50 Hz
≤5
5 A standard
(1 A on request)
0.5 / 1
21 x 14 or 31 x 11
IEC 60185
Burden (VA)
Class 0.5 1 3
100 A 3
150 A 3 4
200 A 3 4
250 A 5 8
300 A 5 8
400 A 6 10
500 A 6 10
600 A 6 10
See pag. 101
Types TADK TADK2 TAD 2 TAD 3
Cable/Bus-bar type current
transformers. Standard
output 5 A (1 A on request).
Rated primary currents
from 40 to 2000 A.
DIN-rail or panel mounting.
115.5 x 75 x 44
Current transformer
1-phase AC
40 to 60 Hz
0.72 kV
3 kV/1 min @ 50 Hz
≤5
5 A standard
(1 A on request)
0.5
25 x 3
IEC 60185
Burden (VA)
Class 0.5 1 3
1 A 10
5 A 10
10 A 10
15 A 10
25 A 10
40 A 10
50 A 10
60 A 10
80 A 10
100 A 10
150 A 10
200 A 10
250 A 10
See pag. 101
Current Transformers 1-Phase
Comentarios a estos manuales