
▲
▲
20
■
CT and VT programming; Open collector Pulse
Digital Output Table
The CT is programmable from 1 to 5000, the VT is program-
mable from 1.0 to 199.9 and from 200 to 1999 (CT*VT ratio
limited to 5000). The CT must be programmed before the VT
because the programming of VT depends on the CT value: if
the CT is modified, then the VT value can automatically satisfy
the expression: CT*VT≤5000. If the CT or VT values are
modified, then the display resolution of the variables and of the
“pul” (pulses) parameter changes automatically according to
the table on the following page.
When the CT or VT value is modified, then the energy meters
Useful information
Serial address
19
23
What is Asy
22
19
Example 2 “Use of digital filter”: it’s necessary to stabilize
the displayed value of the V
L1-N
variable that varies between
222V and 228V. The parameters of the digital filter are to be set
as follows:
• rnG: the variable varies within the average value, the ampli-
tude of which is equal to ±1.3% of the variable’s rated value,
calculated as follows:
(228-222)/2=
±
3V
, then
±
3*100/231V
=±1.3% where 231V is
the phase-neutral rated value of a 400V input range). The
“range” parameter, that corresponds to the action range of
the digital filter, is set at a value which is slightly higher than
the percentage amplitude of the fluctuation: e.g. 2%.
• CoE: if the new value acquired by the instrument is within the
filter’s action range, then the new displayed value is calcu-
lated by summing algebraically to the previous value the
variation divided by the filtering coefficient. As a conse-
quence, a value which is higher than this coefficient implies
a longer settling time and therefore improves the stability.
The latter can also be improved by increasing the filtering
coefficient: the admitted values are within 1 and 16. Enter the
value in consecutive attempts until you reach the desired
stability.
Comentarios a estos manuales