2 Specifications are subject to change without notice WM24-96DS0403
WM24-96
no parity, 1 stop bit
Baud-rate 9600 bauds
Protocol MODBUS/JBUS (RTU)
other characteristics as per RS422/485
Pulse outputs (on request)
Number of outputs up to 2
Type
programmable from 1 to 1000
pulses
V
ON
1.2 VDC/ max. 100 mA
V
OFF
30 VDC max.
Outputs conectable to the
total and/or partial energy
meters
Pulse duration
220 ms (ON), 220 ms (OFF)
according to DIN43864
Insulation By means of optocuplers,
4000 V
RMS
output to measu-
ring inputs,
4000 V
RMS
output to power
supply input.
Notes The outputs can be either
open collector type or relay
type (for the relay outputs
refer to the specifications
described in the “alarm out-
puts”).
RS422/RS485 (on request)
Multidrop
bidirectional (static and
dynamic variables)
Connections 2 or 4 wires, max. distance
1200m, termination directly
on the instrument
Addresses 255, selectable by key-pad
Protocol MODBUS/JBUS (RTU)
Data (bidirectional)
Dynamic (reading only) System and phase variables:
see table “display pages”
Static (writing only) All the configuration parameters,
activation of the static output.
Data format 1 start bit, 8 data bit,
no parity,1 stop bit
Baud-rate 9600 bauds
Insulation By means of optocouplers,
4000 V
RMS
output to
measuring input
4000 V
RMS
output to
supply input
RS232 (on request)
bidirectional (static and
dynamic variables)
Connections 3 wires, max. distance 15m,
Data format 1 start bit, 8 data bit
Number of measure inputs
Current 3
Voltage 4
Digital inputs (on request)
AQ1038 Number of inputs: 3 (voltage
free)
Reading voltage 24VDC/1mA
Input frequency Max. 20Hz, dutycycle 50%
Contact 1 purpose key-pad programming lock
(when the contact is closed).
Contact 2-3 purpose To b e u s e d i n 3 d i f f e re n t w a y s :
• time period selection
(t1-t2-t3-t4) and W
dmd
,
VA
dmd
synchronization;
• Gas total meter, and night
and day tariffs selections
• GAS and WATER, total
meters;
AQ1042 Number of inputs:
3+excitation output (AUX)
(16V<Aux<24VDC, max 15mA)
other characteristics like
AQ1038
Accuracy
(display, RS232, RS485) Ib:5A; Pn= Ib* Un
Current 0.003Ib to 0.2Ib: ±(0.5%
(@ 25°C ± 5°C, R.H. 60%) RDG + 3DGT); 0,2Ib to
Imax: ±(0.5 RDG + 1DGT)
Phase-neutral voltage Range Un: ±(0.5% RDG
(@ 25°C ± 5°C, R.H. 60%) + 1DGT)
Frequency ±0.1 Hz
Active power/energy Class 1 according to
(@ 25°C ± 5°C, R.H. 60%) EN61036 (I start-up: 20mA)
Reactive power/energy Class 2 according to
(@ 25°C ± 5°C, R.H. 60%) EN61268 (I start-up: 20mA)
Apparent power
(@ 25°C ± 5°C, R.H. 60%) ±(1% Pn +2DGT)
Ib:1A; Pn= Ib* Un
Current 0.02Ib to Ib:
(@ 25°C ± 5°C, R.H. 60%) ±(0.5%RDG + 3DGT);
Phase-neutral voltage Range Un:
(@ 25°C ± 5°C, R.H. 60%) ±(0.5% RDG +1DGT)
Frequency ±0.1 Hz
Active power 0.5Ib to Ib: ±(1%RDG +1DGT)
(@ 25°C ± 5°C, R.H. 60%) 0.02Ib to 0.5Ib:
±(1.5%RDG +3DGT)
Reactive power 0.5Ib to Ib: ±(2%RDG +1DGT)
(@ 25°C ± 5°C, R.H. 60%) 0.02Ib to 0.5Ib:
±(3%RDG +3DGT)
Temp e r at ure d rift
200ppm/°C
Display Back-lighted LCD 4x3
1
/
2
digits
(instantaneous variables) or
1x7
1
/
2
digits (energy, gas,
water) 70 x 38mm
Display refresh time 700ms
Measurements Current, voltage, power,
power factor, frequency,
energy. TRMS measurement
of a distorted wave.
Coupling type Direct
Input impedance
208VLL 5(6)AAC (AV4): >200 k
400VLL 5(6)AAC (AV5): >900 k
100VLL 5(6)AAC (AV6): >200 k
660VLL 5(6)AAC (AV7): >900 k
Output Specifications
Input Specifications