18
Programming
Digital Filter
13
Energy Meters Menu
9
20
22
S
▲
▼
❑ Alarm Digital Output
This function allows the
user to set the parameters of the
alarm digital output. Choose the
“diGout1- ALr” function by means
of the keys: to enter the
menu press . Then, set the fol-
lowing parameters:
VAr: choose the variable to be
associated to the alarm activation
by means of the and keys
and confirm with .
rnG: choose the decimal point
position.
on: activation set-point, value of the
variable over which the alarm is acti-
vated. Select the value of the variable
by means of the and keys
and confirm it with ;
oFF: deactivation set-point, value of
the variable over which the alarm is
deactivated. Select the value of the
variable by means of the and
keys and confirm it with ;
nd: normally de-energized output
when there is no alarm.
nE: normally energized output
when there is no alarm.
Select the output status by means
of the and keys and con-
firm it with ;
S
▼▲
S
▼
▲
S
▼▲
S
▼▲
S
▼▲
▲
▼
▲
1.2..
..2.1
▼
▲
1.2..
..2.1
▼
S
S
S
S