CARLO GAVAZZI UDM 40 - PROGRAMMING Manual de usuario Pagina 5

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 23
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 4
5
CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
UDM - USC
V1 R1
Page
5
command.
IMPORTANT: if the address is 00 (zero) all the instruments connected to the network will execute
the command but won’t send an answer frame.
If the request frame contains an invalid function, the answer frame will be an “exception response”.
Exception response
1.2.6 Address
Function Diagnostic code Value CRC
1 byte 1 byte 2 byte 2 byte 2 byte
From 1 to 255 88h 00h 00h AAh 55h MSB LSB
1.3 MEMORY AREA
UDM and USC manage two different memory areas addressed as follows.
Function 03h, 04h and 06h:
Memory area Area
Internal RAM
From 3001h to 3006h
Data storage EEPROM
From E000h to E071h
1.4 UDM AND USC IDENTIFICATION CODE
Every Carlo Gavazzi instrument is identified by means of a code in order to recognise the type of the
instrument via serial communication.
The UDM and USC family codes are:
- 1Ah LSX and LSE module
- 1Bh HSX module
- 1Ch TRX module.
These codes can be read with the following fixed frame:
Instrument code request frame (8 byte):
01h
04h
00h
0Bh
00h
01h
40h
08h
LSX or LSE code answer frame (7 byte):
01h
04h
02h
00h
1Ah
38h
FBh
HSX code answer frame (7 byte):
01h
04h
02h
00h
1Bh
F9h
3Bh
TRX code answer frame (7 byte):
01h
04h
02h
00h
1Ch
B8h
F9h
Vista de pagina 4