Programming
Reset of max and min values
11
Harmonic distortion
7
17
17
rnG: select the position of the
digital point;
Set-on: activation set-point,
value of the variable over which
the alarm is activated. Select the
value of the variable by means of
the and keys and con-
firm with ;
Set-oFF: deactivation set-point,
value of the variable over which
the alarm is deactivated. Select
the value of the variable by
means of the and keys
and confirm it with ;
nd: normally de-energized out-
put when there is no alarm.
nE: normally energized output
when there is no alarm.
Select the output status by
means of the and keys
and confirm it with ;
SEC: delay time at the activation
of the alarm output. Choose the
value of the delay time in sec-
onds by means of the and
keys (up to 255 seconds)
and confirm with .
S
S
S
S
S
S
S
S
S
Digital Output 2
on page 14
1.2..
..2.1
1.2..
..2.1
1.2..
..2.1